OSHA initiated a PSM inspection under the agency's Site Specific Targeting program for industries with high injury and illness rates and its Process Safety Managed Covered Chemical Facilities National Emphasis Program. Eight of the 15 serious violations are related to the Process Safety Management Program for the maintenance and operation of the Anhydrous Ammonia refrigerant system to prevent potentially catastrophic releases. The violations include failing to inspect and test equipment intended to control and contain ammonia; failing to maintain process equipment in an acceptable working order; and not ensuring that process information is up to date and accurate. The company was also cited for failing to provide emergency eyewash, not having an audiometric testing program, and improper chemical storage. Proposed penalties are $76,500.  Here is a breakdown of the citations:

NOTE: Anyone in the refrigeration industry following “IIRA/ASME-15”?  LOL, there is one citation that will be thrown-out!  There are a few other "odd" citations such as Citation 1 Item 1 for not having a exhaust fan switch outside the engineroom was a "general duty clause" citation????

Comments   

#3 Shane 2015-07-17 15:58
:zzz ok I see now , 18 and 20 hr. shifts for the last month must be getting to me.
#2 Bryan 2015-07-17 14:49
Shane, Look closely at the RAGAGEP OSHA referenced in their citation. There is no such organization called IIRA - there is of course IIAR and ASME does not have a 15 - but there is an ASHRAE-15. That is why I said the citation would be thrown out, OSHA did not cite the correct RAGAGEP. Spelling means something in RAGAGEPs! Of course a machinery room needs to have switches outside, per ASHRAE-15 and ANSI/IIAR-2.
#1 shane 2015-07-17 04:36
Why would you not be following “IIRA/ASME-15”?
Why would you think that a fine for not being able to start and stop the ventilation system from outside the engine room would be thrown out?

You have no rights to post comments

 
View 's profile on LinkedIn

 

 LinkedIn Group Button

facebookIcon

 

Partner Organizations

 Chlroine Institute Logo 100 years

I am proud to announce that

The Chlorine Institute and SAFTENG

have extended our"Partners in Safety" agreement

for another year (2024)

CI Members, send me an e-mail

to request your FREE SAFTENG membership

 

RCECHILL BW

  

kemkey logo

OHS Solutions logoCEMANE power association logo

 EIT LOGO

 

Member Associations

ASME logo

 

Screen Shot 2018 05 28 at 10.25.35 PM

aiche logo cmyk highres

Chlorine institute

 nfpa logo.5942a119dcb25

 

TOCAS

 

BLR Logo 2018

 

 

 

 

safteng man copy

 

 organdonor